Errors and recovery

When the driver detects a fault it stops the motor, goes to idle, turns the status LED on steadily and sets the error bit in every CAN frame it sends. It stays there until the error is cleared.

Seeing the error

  • The LED: on and not flashing means error mode (or not calibrated). Three short flashes and a pause is normal operation; fast flashing is calibration.
  • #Error prints In error state! or No errors!, followed by one line per active error.
  • Send_Respond_State_of_Errors returns every flag as a bit; the error bit of any frame says whether there is one.
Normal operation Calibration Error mode
Three short flashes and a pause Fast flashing during calibration On, steady

In error mode the LED does not flash: it stays on, as in the photo on the right.

The errors

Error #Error line Cause What to do
Vbus Vbus error the supply voltage is below 9 V or above 29 V (#Vmax, 29000 mV after #Default) check the supply and the cable; a decelerating motor can push the voltage up
Encoder Encoder error the encoder reports no magnet: missing, too far away or too weak magnet distance and type, see The encoder magnet
Driver Driver error (undervoltage, thermal shutdown, or overcurrent) reserved: this firmware never raises it, because it does not monitor the driver stage —
Velocity Velocity error the speed passed 30,000,000 ticks/s, a fixed threshold that #Vlimit does not change; in practice only a runaway reaches it check the magnet and the calibration
Temperature Temp error the thermistor reads more than #Tlim (75 °C by default), with #Term 1 let the motor cool; lower the current limit
E-stop Received ESTOP command Send_ESTOP was received clear it when it is safe
Watchdog Watchdog error no motion frame or status request within the watchdog time (Send_Watchdog) the host stopped sending; fix the host, then clear
Not calibrated Not calibrated the motor has not been calibrated since #Default, or the EEPROM is invalid run #Cal and #Save
Current Current error reserved; this firmware never raises it —

Clearing

#Clear or Send_Clear_Error clears the flags and goes to idle. An error whose cause is still present comes straight back: a Vbus error at 2 V stays until the supply is right; once the supply is 24 V, one #Clear returns the driver to normal operation. The calibration error clears only by calibrating (or, for a motor you know is calibrated, #Calibrated 1). A gripper E-stop comes back on every control cycle until its E-stop bit is 0 again: #Gripstop 0, or a Send_gripper_data_pack with the bit clear; then clear. While it is active, #Error prints only In error state!.

When the driver does not answer

  • No LED at all: no power. Check DC+ and DC− and the cable orientation.
  • LED on, no answer on UART: the baud rate (256000), TX and RX crossed, the adapter's port.
  • No answer on CAN: the node ID, the termination (about 60 Ω across the bus, unpowered), 1 Mbit/s on the adapter.
  • #Info shows -1 or nonsense: with firmware 106 and newer this should not happen, because the driver replaces a damaged configuration block with the defaults at power-up. If it does, #Default, then calibrate again.

Troubleshooting goes through the symptoms one by one.