Emergency stop wiring¶
Stub.
The two channels¶
The connector panel has two E-stop channels, each a pair of terminals in the two-by-two block to the right of the numbered terminals: E-Stop 1 is E2 and E4, E-Stop 2 is E1 and E3 (E2 and E1 on top, E4 and E3 below). How the runtime reads them depends on the board:
| Board | Channels the runtime reads |
|---|---|
| PCB v1 | E-Stop 1 only. E-Stop 2 always reads pressed, a fault in the board's layout, so the runtime ignores it |
| PCB v2 | Both, cross-checked: either channel pressed stops the robot. The two disagreeing for more than 200 ms is a channel fault, logged as E-stop CHANNEL FAULT and treated as pressed |
PCB v1: wire the E-stop to E-Stop 1
On a PCB v1 board, connect the E-stop button to E-Stop 1, terminals E2 and E4. A button on E-Stop 2 alone stops nothing.
The board's version¶
The board does not report its version. The runtime takes it from config/system.xml, and that number decides which
channels it reads:
Keep it right: a wrong number gives the wrong E-stop policy. The version is on the label inside the box (Versions & compatibility).
The runtime's pin map, docs/pin_map.md at 3.0.1, has every terminal of the connector panel.