Encoder table and anti-cogging

Firmware 109 measures two corrections on the drive itself, with nothing but the motor on the bench. The encoder table corrects the small error of the encoder's angle reading. The anti-cogging is a current that cancels the motor's own torque ripple.

After a calibration both run by themselves (What follows the calibration). This page explains what they are, how to run them again, and how to check them.

The motor turns

Each run turns the motor one revolution forward and one back, slowly. Keep the shaft free: nothing on it and nothing it could drive. A mechanism that cannot turn a whole revolution, a gripper's racks for example, has to come off first.

The encoder table

The magnetic encoder reads the shaft angle with a small error that changes slowly around the turn. The magnet is never exactly on the axis, and the chip itself is not perfectly linear. On the bench NEMA 17 it was 0.61° peak to peak.

The commutation multiplies it by the pole pairs. On a 50-pole-pair stepper the field is then up to about 18 electrical degrees off at places: the 0.61° spans about 31° electrical, and the electrical offset sits near its middle. That costs torque and makes the current uneven around the turn.

To measure it, the driver turns the field open loop, one shaft revolution forward and one back at 2048 ticks/s (about 20 s). A current of 80 % of the current limit holds the rotor to the field.

At each 1/128 of a turn it records how far the encoder's angle is from the field's. Forward and backward are averaged, so friction, which pulls the rotor behind the field in each direction, cancels. The stepper's own pull towards its detents is left out by keeping only the harmonics 1 to 16 per turn.

Illustration, not a measurement: friction pulls the forward and the backward pass to either side of the encoder's error, and the detents add a fast ripple; their average, kept to the harmonics 1 to 16 per turn, is the table. Illustration, not a measurement: friction pulls the forward and the backward pass to either side of the encoder's error, and the detents add a fast ripple; their average, kept to the harmonics 1 to 16 per turn, is the table.
Figure 5.6: Illustration, not a measurement: friction pulls the forward and the backward pass to either side of the encoder's error, and the detents add a fast ripple; their average, kept to the harmonics 1 to 16 per turn, is the table.

The result is a table of 128 corrections. From then on the encoder reading is corrected with it. The electrical offset is moved by the table's mean error, so the commutation stays right.

The encoder table of the bench NEMA 17: the encoder's error at each 1/128 of a turn, 0.61° peak to peak, about 31° electrical on the right-hand scale; the dashed line is its once-per-turn part. The encoder table of the bench NEMA 17: the encoder's error at each 1/128 of a turn, 0.61° peak to peak, about 31° electrical on the right-hand scale; the dashed line is its once-per-turn part.
Figure 5.7: The encoder table of the bench NEMA 17: the encoder's error at each 1/128 of a turn, 0.61° peak to peak, about 31° electrical on the right-hand scale; the dashed line is its once-per-turn part.

A table over 4° peak to peak, or one that would move the offset by more than 60 electrical degrees, is rejected as implausible: the magnet is loose or far off its place.

Anti-cogging

A stepper pulls towards its detent positions, four times per electrical turn. Errors in the current measurement add a ripple once and twice per electrical turn.

At low speed both show as a ripple in the speed and the position. Anti-cogging adds a current to the current setpoint that cancels it: a function of the electrical angle, added in velocity and position modes.

To find it, the driver runs in velocity mode at 1500 ticks/s (parameter 44), one motor revolution forward and one back. It records the current the velocity loop asks for in 256 bins over the electrical angle. Then it averages the two directions, each without its mean, so friction drops out.

From that it keeps two forms of the same correction:

  • harmonics (parameter 37 = 1): the 8 largest of the harmonics 1 to 32 of the electrical angle, each a·cos(h·θ) + b·sin(h·θ) in mA;
  • table (parameter 37 = 2): 256 values in mA over one electrical turn, interpolated between them.
The anti-cogging of the bench NEMA 17 over one electrical turn, identified at 1500 ticks/s before the drive had the encoder table and the zero trim: above, its two forms; below, the current the velocity loop asks for with it off and on. The anti-cogging of the bench NEMA 17 over one electrical turn, identified at 1500 ticks/s before the drive had the encoder table and the zero trim: above, its two forms; below, the current the velocity loop asks for with it off and on.
Figure 5.8: The anti-cogging of the bench NEMA 17 over one electrical turn, identified at 1500 ticks/s before the drive had the encoder table and the zero trim: above, its two forms; below, the current the velocity loop asks for with it off and on.

The identification switches the harmonics on. On the bench both forms were equally good. Parameter 38 scales the correction from 0 to 200 % for experiments; 100 % is as identified.

The angle here comes from the encoder alone, without the calibration's offset. The part of the correction that comes from the current measurement is tied to the motor's electrical angle, though, which the offset defines. That is why #Calangle identifies the anti-cogging again.

The identification records the current the loops ask for, so it depends a little on the gains. After a large change of the current or velocity gains, identify it again.

The current-sense zero trim

The once-per-electrical-turn part of the anti-cogging is mostly an error of the current-sense zero. On the bench it was 1.6 mA of ripple per ADC count of zero error.

The identification with the trim reads both zero errors from it and corrects the zeros. Then it identifies again on the corrected zeros.

The harmonics of the anti-cogging the drive identified on the bench NEMA 17, with the current-sense zeros as measured and with the zeros corrected by hand, as the trim corrects them: the 1st harmonic drops, the 2nd and 4th stay. The harmonics of the anti-cogging the drive identified on the bench NEMA 17, with the current-sense zeros as measured and with the zeros corrected by hand, as the trim corrects them: the 1st harmonic drops, the 2nd and 4th stay.
Figure 5.9: The harmonics of the anti-cogging the drive identified on the bench NEMA 17, with the current-sense zeros as measured and with the zeros corrected by hand, as the trim corrects them: the 1st harmonic drops, the 2nd and 4th stay.

If the 1st harmonic did not drop by at least 30 % and is still above 2.0 mA, the zeros go back. The anti-cogging is then identified once more without the trim, and the state reads 11, done without the trim.

A 1st harmonic under 1.5 mA is left alone, and one run moves a zero by at most 30 counts.

The trims (parameters 59 and 60, up to ±60 counts) are saved with the encoder table. They are added to the zero the driver measures at every start-up. On the bench drive the trim took the 1st harmonic from 8.8 to 0.2 mA in one run. The plot above shows a correction by hand, 8.9 to 1.0 mA; the drive's own trim did better.

Running them

The driver must be calibrated and without an error. Each run has a UART command and a CAN parameter:

What UART CAN: Send_Parameter
the encoder table, used at once #Encal 52 = 1
the encoder table, used and saved #Encal save 52 = 2
the encoder table, then the anti-cogging with the trim, then save all #Encal all 52 = 3, or 43 = 3
the anti-cogging, switched on #Cogcal 43 = 1
the anti-cogging, switched on and saved #Cogcal save 43 = 2
the anti-cogging with the trim #Cogcal trim 43 = 4
the anti-cogging with the trim, saved #Par 43,5 43 = 5
stop a run #Encal stop, #Cogcal stop 52 = 0, 43 = 0

#Encal stop does not stop the anti-cogging part of a combined run (#Encal all). #Cogcal stop stops a run in either part, and so do 52 = 0 and 43 = 0 over CAN.

  1. Make sure the shaft is free: nothing on it and nothing it could drive.
  2. Send the run's command from the table, on the UART or over CAN.
  3. Send nothing else while the motor turns, one revolution forward and one back for each run.
  4. Read the result with #Encal state or #Cogcal state, or parameter 52 or 43 over CAN.

Check

The state reads 3, done, or 11, done without the trim. The motor holds the position the shaft reached. Any other state is in the table "When a run fails" under Checking them.

Both runs keep the CAN watchdog fed while they go, and end by holding the position the shaft reached. They stop at once when a host sends a command (a motion command, Idle) or an error comes up. Nothing is saved then.

While a run turns the motor a capture is not armed. During the anti-cogging run parameters 34 and 35 refuse a write: the runs use the capture's memory and the histogram.

A save from a run is the whole configuration, as #Save writes it. After a change of the motor, the magnet or its position, run the encoder table and the anti-cogging again, in that order, or calibrate again.

Two guards keep a correction from running on the wrong data:

  • parameter 37 refuses 1 or 2 while no set is stored for that form;
  • an encoder table measured on its own (52 = 1 or 2) switches an anti-cogging set from before off, because that set was found on the uncorrected encoder. The anti-cogging state then reads 10 until it is identified again.

Checking them

#Info ends with what is in force:

In force:
  encoder table: on, error 0.61 deg p-p
  anti-cogging: on (harmonics), saved
  current-sense zero trim: -1 / 5 counts
  delay compensation: 166 us
  speed estimate: direct PLL, 60 Hz
  fast reading / fast PWM: on / on
  input filter: off; integral deadband: off
  after #Calangle (parameter 56): anti-cogging, then save

The example shows the values the bench drive measured. While a run goes, a line running: encoder table or running: anti-cogging identification follows.

#Encal state and #Cogcal state print one run's state without starting it. After a finished identification (state 3, or 11 without the trim) it also lists the harmonics.

Over CAN the same is in the parameters (the parameter table):

Parameter What it tells On the bench NEMA 17
52 the encoder table's state: 3 done, 4 aborted, 5 error or not calibrated, 6 the rotor did not follow, 7 rejected 3
54 the table's error peak to peak, 0.01° of the shaft 61-65 (0.61-0.65°); two runs within 0.021°
55 the amplitude of its once-per-turn part, 0.01° of the shaft 19 (0.19°)
57 how far the last table moved the electrical offset, 0.1° electrical −25, then −1 on a second run
43 the anti-cogging state: 3 done, 11 done without the trim, 6 the shaft did not turn 3
45 the cogging current found, 0.1 mA rms 71 (7.1 mA)
62, 63 the 1st harmonic before and after the trim, 0.1 mA 88, then 2
59, 60 the zero trims, counts −1, 5
79 the bits of what is in force, see What is in force

With the anti-cogging on, the bench motor's speed ripple that repeats with the angle was 1.2 to 2 times smaller at 1500 to 6000 ticks/s. The position ripple was 1.9 to 2.5 times smaller.

The speed of the bench NEMA 17 turning at 6000 ticks/s, minus its mean, before the drive had the encoder table and the zero trim: with the anti-cogging on, the part that repeats with the angle is about half as large. The speed of the bench NEMA 17 turning at 6000 ticks/s, minus its mean, before the drive had the encoder table and the zero trim: with the anti-cogging on, the part that repeats with the angle is about half as large.
Figure 5.10: The speed of the bench NEMA 17 turning at 6000 ticks/s, minus its mean, before the drive had the encoder table and the zero trim: with the anti-cogging on, the part that repeats with the angle is about half as large.

A free motor gains little from the encoder table in these numbers. Its current varied 2.5 to 3 times less around the turn, but a free motor needs little current. A loaded one gains more.

Send_Buffer_Read reads the corrections themselves: kind 4 the encoder table (128 values in 1/16 count), kind 2 the harmonics, kind 3 the anti-cogging table (Respond_Buffer_Data).

When a run fails:

State Cause What to do
52 = 6, 43 = 6 the rotor did not follow: the shaft is blocked, or the current is too low to turn it free the shaft; for the encoder table raise the current limit (it uses 80 % of it)
52 = 5, 43 = 5 the driver was in error or is not calibrated #Error, clear it, calibrate
52 = 4, 43 = 4 a command came first run it again and send nothing meanwhile
52 = 7 the table is implausible check the magnet: glued, centred, at the right distance (The encoder magnet), then calibrate
43 = 8 the encoder table of a combined run failed parameter 52 says why

Switching them off

UART CAN: Send_Parameter
the encoder table off / on #Encal off, #Encal on 53 = 0, 53 = 1
the anti-cogging off, harmonics, table #Par 37,0, #Par 37,1, #Par 37,2 37 = 0, 1, 2
how much of the anti-cogging #Par 38, and the percentage 38 = 0 to 200 (%)

#Save keeps the switches with the corrections. #Default clears both corrections and the trims.