Parameters and buffers

From firmware 109 a setting that has no command of its own is a parameter: a number from 1 to 93 (87 in firmware 109) behind one pair of commands, Send_Parameter (ID 36) to set it and Send_Get_Parameter (ID 37) to read it, answered with Respond_Parameter (ID 38). The identifier has room for only 64 command IDs, so new settings no longer use them up.

Parameter numbers are permanent: a number is never given a new meaning. Number 73 is not used and stays free; 88 and 89 are the Spectral Micro's own, and STEPFOC does not have them.

Firmware 110 adds 90 to 93: the three settings that only UART could set before, #Rstint (90), #Term, the thermistor (91) and #Gripper, gripper mode (92), and the gripper's stroke (93, read only). The Spectral-BLDC library 1.22 names them (PARAM_RSTINT, PARAM_THERMISTOR, PARAM_GRIPPER_MODE, PARAM_GRIPPER_STROKE); 1.21 sets and reads them by their numbers.

The buffers are the larger data a drive holds: a capture of three signals, a histogram, the anti-cogging set and the encoder table. Send_Buffer_Read (ID 41) reads them in 8-byte frames, Respond_Buffer_Data (ID 42) carries them, and Send_Buffer_Write (ID 43) writes the anti-cogging set.

Over UART, #Par does the same: #Par lists every parameter, #Par 56 reads one, #Par 56,0 sets it (Status and utility).

Setting and reading a parameter

A set is not answered: read the value back to know what the driver took. A value outside a parameter's range is clamped, replaced or refused, as the table says, and a read-only number ignores the write.

import Spectral_BLDC as Spectral

comms = Spectral.CanCommunication(bustype='slcan', channel='COM41', bitrate=1000000)
motor = Spectral.SpectralCAN(node_id=0, communication=comms)

motor.Send_Parameter(56, 0)                # nothing runs by itself after the next #Calangle
motor.Send_Get_Parameter(56)               # read it back
message, ids = comms.receive_can_messages(timeout=0.1)
if message is not None:
    motor.UnpackData(message, ids)
print(motor.parameters.get(56))
motor.Send_Save_config()                   # keep it over a power cycle

Send_Parameter, Send_Get_Parameter and the buffer calls need the Spectral-BLDC library 1.21 or newer. Send_Parameter takes the value itself: a gain or a limit (8 to 16 and 20) is sent as a float, so motor.Send_Parameter(16, 1500) sets a current limit of 1500 mA; every other parameter takes a whole number.

The commands

Send_Parameter

ID 36host → driver5 bytesPython: Send_Parameter()

Sets one parameter by its number (the parameter table). Firmware 109 gives new settings a parameter number instead of a command ID of their own, since the identifier has room for only 64 command IDs. A value outside a parameter's range is clamped, replaced or refused as the table says; a number the firmware does not know, or a read-only one, is ignored. The driver does not answer: read the value back with Send_Get_Parameter. A value set this way lives in RAM until Send_Save_config, like every other setting; the table says which parameters Save keeps.

5 bytes

Byte Field Type Meaning
0 Parameter unsigned 8-bit the parameter number, 1-93
1-4 Value signed 32-bit the new value, in the parameter's unit; for the gains, limits and Kt (8-16, 20) a float's bit pattern

The driver does not answer this command.

A data frame of another length, or a remote frame, is ignored and flagged as a wrong data length. It does not reset the watchdog.


Send_Get_Parameter

ID 37host → driver1 bytesPython: Send_Get_Parameter()

Asks for the value in force of one parameter. The answer, Respond_Parameter, comes under ID 38, not 37: a host and a driver must never send data frames with the same identifier, because two sent at the same moment collide. Resets the watchdog. The Python library stores the value in parameters[number].

1 bytes

Byte Field Type Meaning
0 Parameter unsigned 8-bit the parameter number

The driver answers with Respond_Parameter.


Respond_Parameter

ID 38driver → host5 bytes

The answer to Send_Get_Parameter: the number and the value in force. For a number the firmware does not know the frame carries the number alone (1 byte; the Python library sets unknown_parameter). The gains, limits and Kt (parameters 8 to 16 and 20) travel as the bit pattern of an IEEE-754 float, the others as integers.

The frame (5 bytes)

Byte Field Type Meaning
0 parameter unsigned 8-bit the parameter number
1-4 value signed 32-bit the value in force; a float's bits for 8-16 and 20

Send_Buffer_Read

ID 41host → driver5 bytesPython: Send_Buffer_Read()

Asks for entries of one of the drive's buffers: the capture, the histogram, the anti-cogging harmonics or table, or the encoder table. The driver answers with one Respond_Buffer_Data frame per entry (for the two tables, one per three values), sent from its main loop whenever a transmit mailbox is free, so a long read-out never holds up the control loop or other answers. A new request replaces one still in progress; count 0 cancels it. Entries past the end are not sent. Resets the watchdog.

5 bytes

Byte Field Type Meaning
0 Kind unsigned 8-bit 0 capture (up to 1024 samples: parameter 32 says how many), 1 histogram (256 bins), 2 anti-cogging harmonics (8 slots), 3 anti-cogging table (256 values), 4 encoder table (128 values)
1-2 First unsigned 16-bit the first index
3-4 Count unsigned 16-bit how many entries; 0 cancels a read-out

The driver does not answer this command.


Respond_Buffer_Data

ID 42driver → host8 bytes

One entry of a buffer, the answer to Send_Buffer_Read. The first two bytes say which: the kind in the top three bits, the index in the other thirteen (kind × 8192 + index). The six bytes after them depend on the kind, as the table below the frame says.

The frame (8 bytes)

Byte Field Type Meaning
0-1 header unsigned 16-bit kind × 8192 + index
2-3 word_a signed 16-bit capture: channel A; histogram: the count (unsigned); harmonics: the harmonic number (0 = slot unused); tables: entry index
4-5 word_b signed 16-bit capture: channel B; histogram: the sum's upper 16 bits; harmonics: a, the cosine term in mA; tables: entry index + 1
6-7 word_c signed 16-bit capture: channel C; histogram: the sum's lower 16 bits; harmonics: b, the sine term in mA; tables: entry index + 2 (0 past the end)
Kind Index Bytes 2-7
0 capture the sample, oldest first, 0 to parameter 32 − 1 channels A, B and C, each in its signal's unit (the parameter table lists the signals)
1 histogram the bin, 0-255 over one electrical turn or one motor turn the count (unsigned 16-bit), then the sum (signed 32-bit); the bin's mean is sum ÷ count
2 anti-cogging harmonics the slot, 0-7 the harmonic of the electrical angle (1-32, 0 = unused), a and b in mA: the slot adds a·cos(h·θ) + b·sin(h·θ)
3 anti-cogging table the first of three values, 0-255 three values in mA, 64 angle counts apart (256 per electrical turn)
4 encoder table the first of three values, 0-127 three corrections in 1/16 encoder count, 128 per motor turn

Send_Buffer_Write

ID 43host → driver8 bytesPython: Send_Cogging_Harmonic(), Send_Cogging_Table()

Writes the anti-cogging set: kind 2 one harmonic slot per frame, kind 3 three table values per frame, in the Respond_Buffer_Data layout. Other kinds are ignored (the encoder table cannot be written), and so is a harmonic above 32. The set lives in RAM until Send_Save_config; switch it on with parameter 37. The driver does not answer.

8 bytes

Byte Field Type Meaning
0-1 Header unsigned 16-bit kind × 8192 + index; kind 2 or 3
2-3 Word A signed 16-bit kind 2: the harmonic (1-32, 0 = unused); kind 3: value at index
4-5 Word B signed 16-bit kind 2: a in mA; kind 3: value at index + 1
6-7 Word C signed 16-bit kind 2: b in mA; kind 3: value at index + 2

The driver does not answer this command.


Every parameter

The number and the name are read from the firmware; the rest is checked against its source. Access: a read-only parameter ignores a write; a run parameter starts or stops a run when written and gives its state when read.

Watchdog and tool

Parameters 1 to 5 live in settings block 2 of the EEPROM, 6 and 7 in the first settings block beside the other settings; Send_Save_config keeps all seven. A value outside a range is clamped, replaced or ignored, as the Value column says.

No. What it is Value
1 What the drive is built into. For an MSG the tens digit is the rail (1 = 100, 2 = 150, 3 = 200 mm) and the units digit the stepper (1 = 21.5, 2 = 40, 3 = 60 mm). Also #Tool; reported in the identity frame.
PARAM_TOOL_ID · Access: set, read · Kept by Save: yes, settings block 2
0 none, 1 SSG-48, 11-33 MSG, 200-254 your own tools; a value outside 0-255 is ignored. Default 0
2 How long watchdog hold or descend runs before the after-action takes over.
PARAM_WD_FALLBACK_TIME · Access: set, read · Kept by Save: yes, settings block 2
ms, 0-60000 (clamped). Default 2000
3 The current watchdog descend applies. 0 lets gravity lower a joint; a gripper gets its grip current.
PARAM_WD_FALLBACK_CURRENT · Access: set, read · Kept by Save: yes, settings block 2
mA, signed, -32768 to 32767 (outside: 0). Default 0
4 The speed watchdog descend never exceeds, in either direction.
PARAM_WD_FALLBACK_SPEED · Access: set, read · Kept by Save: yes, settings block 2
ticks/s, 0-65535 (outside: 1000). Default 1000
5 What follows hold or descend when the fallback time has run out.
PARAM_WD_AFTER_ACTION · Access: set, read · Kept by Save: yes, settings block 2
0 legacy, 2 brake, 3 coast (any other value: 0). Default 0
6 The watchdog time, the same value Send_Watchdog sets.
PARAM_WD_TIME · Access: set, read · Kept by Save: yes, settings block 1
ms, 0 = off (a negative value: 0). Default 0
7 What a trip of the watchdog alone does, the same value as byte 4 of Send_Watchdog.
PARAM_WD_ACTION · Access: set, read · Kept by Save: yes, settings block 1
0 legacy, 1 hold, 2 brake, 3 coast, 4 descend (outside 0-255: 0; 5-255 act as legacy). Default 0

Gains, limits and settings

The values in force, readable and writable by parameter (their own commands, given in each row, still work). A float travels as its IEEE-754 bit pattern, big-endian, the way the gain commands send it; over UART #Par 9,0.02 sets Kpv. A write goes to RAM like the commands' own; Send_Save_config keeps it. Parameter 23, the product stamp, stays read only.

No. What it is Value
8 Kp of the position loop (Send_Position_Gains, #Kpp).
PARAM_KPP · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
9 Kp of the velocity loop (Send_Velocity_Gains, #Kpv).
PARAM_KPV · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
10 Ki of the velocity loop (Send_Velocity_Gains, #Kiv).
PARAM_KIV · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
11 Kp of the current loops; writing it sets the Iq and the Id loop, as #Kpiq does (Send_Current_Gains sets the Iq loop only). A calibration and parameter 49 set it too.
PARAM_KPIQ · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
12 Ki of the current loops; writing it sets the Iq and the Id loop, as #Kiiq does (Send_Current_Gains sets the Iq loop only). A calibration and parameter 49 set it too.
PARAM_KIIQ · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
13 KP, the stiffness of the impedance (PD) loop (Send_PD_Gains).
PARAM_KP · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
14 KD, the damping of the impedance (PD) loop (Send_PD_Gains).
PARAM_KD · Access: set, read · Kept by Save: yes
float; 0 or more, below 10^9 (negative or not a number: refused)
15 The velocity limit (Send_Limits, #Vlimit).
PARAM_VELOCITY_LIMIT · Access: set, read · Kept by Save: yes
float, ticks/s; 0 or more, below 10^9 (otherwise refused)
16 The current limit (Send_Limits, #Ilim).
PARAM_CURRENT_LIMIT · Access: set, read · Kept by Save: yes
float, mA; 0-2800 (negative or above 2800: refused)
17 The voltage limit of the current loops (Send_Voltage_Limit, #Vlim).
PARAM_VOLTAGE_LIMIT · Access: set, read · Kept by Save: yes
mV, 0-60000 (outside: refused); 0 = the supply voltage
18 The idle behaviour (Send_Settings bit 0, #Brake, #Coast).
PARAM_BRAKE_COAST · Access: set, read · Kept by Save: yes, settings block 2, from firmware 110 (109 braked at every power-up). Never saved, and after #Default: brake
1 brake, 0 coast (any value but 0: brake)
19 The heartbeat interval (Send_Heartbeat_Setup).
PARAM_HEARTBEAT_MS · Access: set, read · Kept by Save: yes
ms, 0-60000 (outside: refused); 0 = off
20 The torque constant (Send_Kt, #Kt, calibration).
PARAM_KT · Access: set, read · Kept by Save: yes
float, Nm/A; 0 or more, below 10^9 (otherwise refused)
23 The product lock: the product that calibrated this board. Stamped at the first start-up of a calibrated board and at every save. A firmware that finds the other product's stamp drives nothing (see Errors).
PARAM_BOARD_PRODUCT · Access: read only · Kept by Save: yes, settings block 2 (stamped by the firmware)
1 STEPFOC, 2 Spectral Micro, 0 none
90 Whether the velocity and current integrators are reset on every new setpoint command (#Rstint). Added in firmware 110.
PARAM_RSTINT · Access: set, read · Kept by Save: yes
0 or 1 (anything else: refused). Default 0
91 The thermistor measurement and the temperature error (#Term). Added in firmware 110.
PARAM_THERMISTOR · Access: set, read · Kept by Save: yes
0 off, 1 on (anything else: refused). Default 0
92 Gripper mode (#Gripper), in force at once: the driver then reads its commands as a gripper, or as a motor. It is written only while the driver is idle, so a move is never cut over half-way. Added in firmware 110.
PARAM_GRIPPER_MODE · Access: set, read · Kept by Save: yes
0 or 1 (anything else, or a write while the driver is not idle: refused). Default 0

The motor

No. What it is Value
76 The phase resistance of one coil, the same value as #R (in Ω there). The current gains follow at the next calibration or when parameter 49 is written.
PARAM_R_MOHM · Access: set, read · Kept by Save: yes, with the calibration
mΩ, 1-100000 (outside: refused)
77 The phase inductance of one coil, the same value as #L (in H there). The current gains follow at the next calibration or when parameter 49 is written.
PARAM_L_UH · Access: set, read · Kept by Save: yes, with the calibration
µH, 1-1000000 (outside: refused)
78 The motor's pole pairs, the same value as #PP. Calibrate after a change.
PARAM_POLE_PAIRS · Access: set, read · Kept by Save: yes, with the calibration
1-200, only while the driver is idle (otherwise refused); calibration accepts 50, 75, 100 and 125

Current sensing and the current loop

The current-sense zero is the ADC reading with no current flowing, in counts from 2048 (1 count is about 1.6 mA). The driver measures it at every start-up with the bridge off; the trim is added to it.

No. What it is Value
21 The current-sense zero of channel 1 in use. Measured at start-up (the trim, 59, added); writable for tests, until the next start-up.
PARAM_SENSE1_OFFSET · Access: set, read · Kept by Save: no: measured again at every start-up
counts from 2048, -400 to 400 (outside: refused)
22 The current-sense zero of channel 2 in use, as 21.
PARAM_SENSE2_OFFSET · Access: set, read · Kept by Save: no: measured again at every start-up
counts from 2048, -400 to 400 (outside: refused)
40 The zero of channel 1 measured with the bridge off, the trim added.
PARAM_SENSE1_OFFSET_OFF · Access: read only · Kept by Save: no: measured at every start-up
counts from 2048
41 The zero of channel 2 measured with the bridge off, the trim added.
PARAM_SENSE2_OFFSET_OFF · Access: read only · Kept by Save: no: measured at every start-up
counts from 2048
42 The second zero measurement, made in idle after start-up with the bridge switching at 50 % duty. On the bench it made the current ripple worse, so it is measured and kept but not used unless 46 asks for it.
PARAM_SENSE_ZERO_SWITCHING · Access: read only · Kept by Save: no
0 not run, 1 measuring, 2 in use, 3 rejected (implausible), 4 interrupted (a command or an error came first), 5 measured, not in use
46 Which zero is in use. 1 takes effect only while 42 reads 5 (measured, not in use).
PARAM_SENSE_ZERO_USE_SWITCHING · Access: set, read · Kept by Save: no
1 the zero measured with the bridge switching, 0 the bridge-off zero. Default 0
47 The zero of channel 1 measured with the bridge switching.
PARAM_SENSE1_OFFSET_SW · Access: read only · Kept by Save: no
counts from 2048
48 The zero of channel 2 measured with the bridge switching.
PARAM_SENSE2_OFFSET_SW · Access: read only · Kept by Save: no
counts from 2048
49 Writing it sets Kp_iq and Ki_iq at once from R, L and this bandwidth, as #Cbw does. Reading gives the bandwidth the gains in force amount to with the R and L in force (0 without them).
PARAM_CURRENT_BANDWIDTH · Access: set, read · Kept by Save: no; the gains it sets are kept by Save
Hz, 10-625 (outside, or with R or L not set: refused). 160 at every start-up
58 The d-axis current setpoint, as #Id. It makes no torque, only more current in the coils.
PARAM_ID_SETPOINT · Access: set, read · Kept by Save: no
mA, -3000 to 3000 (outside: refused). Default 0
59 The trim added to the zero of channel 1 measured at every start-up. The anti-cogging identification with the trim (43 = 4 or 5, and the runs after a calibration) sets it; writing it moves the zero in use at once.
PARAM_ZERO_TRIM1 · Access: set, read · Kept by Save: yes, encoder block
counts, -60 to 60 (outside: refused). Default 0
60 The trim of channel 2, as 59.
PARAM_ZERO_TRIM2 · Access: set, read · Kept by Save: yes, encoder block
counts, -60 to 60 (outside: refused). Default 0
61 The electrical offset between the encoder and the motor, found by calibration (#Offset in rad).
PARAM_THETA_OFFSET · Access: read only · Kept by Save: yes, with the calibration
0.1° electrical
62 The 1st harmonic of the anti-cogging set before the last trim, the error the trim corrects.
PARAM_TRIM_H1_BEFORE · Access: read only · Kept by Save: no
0.1 mA
63 The 1st harmonic after the last trim. A trim that does not lower it by 30 % is taken back.
PARAM_TRIM_H1_AFTER · Access: read only · Kept by Save: no
0.1 mA
64 Commutation delay compensation: the output voltage is turned forward by the angle the rotor covers in this time. Applied in the closed-loop modes above 100 ticks/s.
PARAM_COMM_DELAY_US · Access: set, read · Kept by Save: no: 166 at every start-up
µs, 0-500 (outside: refused), 0 = off. Default 166
65 Where the transforms of every control loop take sin and cos from. The table was not faster on the bench.
PARAM_FAST_TRIG · Access: set, read · Kept by Save: no
1 from the integer sine table, 0 from the float routine. Default 0

Speed estimate and the velocity loop

No. What it is Value
50 The speed the loops, the watchdog descend, telemetry and the capture use. Calibration and the gripper's stop detection always use the moving average.
PARAM_SPEED_ESTIMATOR · Access: set, read · Kept by Save: no: 2 at every start-up
0 moving average, 1 PLL, 2 direct PLL (outside: refused). Default 2
51 The natural frequency of both PLLs.
PARAM_SPEED_PLL_BANDWIDTH · Access: set, read · Kept by Save: no: 60 at every start-up
Hz, 10-312 (outside: refused). Default 60
74 The position input filter, position and PD modes: a critically damped filter between the host's position setpoints and the loops, which also makes the speed from them. Only for hosts that send positions without the speed; about the host's setpoint rate ÷ 12.
PARAM_INPUT_FILTER_HZ · Access: set, read · Kept by Save: no
Hz, 0-250 (outside: refused), 0 = off. Default 0
75 Position mode: the velocity integral sees the position error less this band, so a holding motor stops pushing against a small error. It trades holding current for accuracy.
PARAM_VEL_INT_DEADBAND · Access: set, read · Kept by Save: no
ticks, 0-2000 (outside: refused), 0 = off. Default 0

Anti-cogging

No. What it is Value
37 Which form of the stored anti-cogging is added to the current setpoint in velocity and position modes. 1 or 2 is refused while the stored set holds nothing for that form: read it back.
PARAM_COGGING_MODE · Access: set, read · Kept by Save: yes, anti-cogging block
0 off, 1 harmonics, 2 table. Default 0
38 How much of the stored anti-cogging is applied.
PARAM_COGGING_SCALE · Access: set, read · Kept by Save: yes, anti-cogging block
percent, 0-200 (clamped). Default 100
43 The anti-cogging identification on the drive: one motor turn forward and one back in velocity mode at the speed of 44. The shaft must be free to turn. A command from a host or an error aborts it.
PARAM_COGCAL · Access: set starts or stops a run; read gives its state · Kept by Save: the result, when started with 2, 3 or 5
Write 0 abort, 1 identify, 2 identify and save, 3 encoder table, then anti-cogging, then save all, 4 identify with the current-sense zero trim, 5 the same and save. Read 0 idle, 1 turning forward, 2 turning backward, 3 done (harmonics on), 4 aborted, 5 failed (an error, or not calibrated), 6 failed (the shaft did not turn), 7 a combined run is measuring the encoder table, 8 the combined run's encoder table failed (52 says why), 9 not used, 10 switched off (the encoder table was measured again on its own), 11 done without the trim
44 The speed the identification turns at.
PARAM_COGCAL_SPEED · Access: set, read · Kept by Save: no
ticks/s, 100-20000 (clamped). Default 1500
45 The cogging current the last identification found, rms.
PARAM_COGCAL_RIPPLE · Access: read only · Kept by Save: no
0.1 mA rms

Encoder table

No. What it is Value
52 Measures the encoder table: the field turns the rotor open loop one shaft turn forward and one back at 2048 ticks/s (about 20 s). The shaft must be free.
PARAM_ENCAL · Access: set starts or stops a run; read gives its state · Kept by Save: the table, when started with 2 or 3
Write 0 abort, 1 measure and use, 2 measure, use and save, 3 then the anti-cogging and save all. Read 0 idle, 1 turning forward, 2 turning backward, 3 done (in use), 4 aborted, 5 failed (an error, or not calibrated), 6 failed (the rotor did not follow the field), 7 rejected (over 4° peak to peak, or an offset move over 60° electrical)
53 Corrects the encoder reading with the table.
PARAM_ENCAL_USE · Access: set, read · Kept by Save: yes, encoder block
1 on, 0 off; 1 only when a table was measured; refused while one is being measured
54 The table's error, peak to peak (0 without a table).
PARAM_ENCAL_PP · Access: read only · Kept by Save: with the table
0.01° of the shaft
55 The once-per-turn part of the error, its amplitude (mostly a magnet off the axis).
PARAM_ENCAL_ONCE · Access: read only · Kept by Save: with the table
0.01° of the shaft
56 What follows a #Calangle: any value but 0 identifies the anti-cogging again and saves the whole configuration. #Cal does not read it: it always runs the encoder table and the anti-cogging, and #Calonly never does.
PARAM_AFTER_CAL · Access: set, read · Kept by Save: yes, encoder block
0 nothing, 1 or 2 anti-cogging (outside: refused). Default 2 on a drive with no encoder block saved
57 How far the last encoder-table run moved the electrical offset.
PARAM_ENCAL_OFFSET · Access: read only · Kept by Save: no
0.1° electrical

Capture and histogram

The signal numbers: 0 none, 1 measured Iq (mA), 2 measured Id (mA), 3 Iq setpoint with the anti-cogging (mA), 4 speed (ticks/s, saturates at ±32767), 5 speed ÷ 16, 6 position (ticks, the low 16 bits), 7 position error (ticks), 8 electrical angle (0-16383 per electrical turn, from the encoder alone), 9 encoder (0-16383 per motor turn), 10 Vbus (10 mV), 11 and 12 the two current-sense readings (counts after the zero), 13 the control interrupt's time (µs), 14 the anti-cogging feedforward (mA), 15 the Iq setpoint without the anti-cogging (mA), 16 the Uq setpoint (mV), 17 and 18 the d and q voltage the output transform received (mV). None of these settings is saved.

No. What it is Value
24 The signal of channel A, which is also the trigger channel.
PARAM_CAPTURE_SOURCE_A · Access: set, read · Kept by Save: no
signal 0-18 (outside: 0). Default 4, speed
25 The signal of channel B.
PARAM_CAPTURE_SOURCE_B · Access: set, read · Kept by Save: no
signal 0-18 (outside: 0). Default 1, Iq
26 The signal of channel C.
PARAM_CAPTURE_SOURCE_C · Access: set, read · Kept by Save: no
signal 0-18 (outside: 0). Default 8, electrical angle
27 One sample every N control loops of 160 µs.
PARAM_CAPTURE_DIVIDER · Access: set, read · Kept by Save: no
control loops per sample, 1-65535 (clamped). Default 1
28 1 to 4 clear the buffer and arm a capture; 0 stops one and keeps what was recorded. The error trigger fires when the error flag rises, a watchdog trip included; an error already present does not fire it.
PARAM_CAPTURE_TRIGGER · Access: set, read · Kept by Save: no
0 stop, 1 now, 2 on an error, 3 channel A rising through the level, 4 falling through it (outside: 0)
29 The level of triggers 3 and 4.
PARAM_CAPTURE_LEVEL · Access: set, read · Kept by Save: no
channel A's unit, -32768 to 32767 (saturated). Default 0
30 How many samples from before the trigger the capture keeps.
PARAM_CAPTURE_PRETRIGGER · Access: set, read · Kept by Save: no
samples, 0-1023 (clamped). Default 0
31 Where the capture stands.
PARAM_CAPTURE_STATE · Access: read only · Kept by Save: no
0 idle, 1 armed, 2 recording, 3 done
32 The samples readable with buffer kind 0.
PARAM_CAPTURE_COUNT · Access: read only · Kept by Save: no
samples, 0-1024
33 Which sample of the read-out is the trigger sample.
PARAM_CAPTURE_TRIGGER_INDEX · Access: read only · Kept by Save: no
sample index; -1 before a trigger
34 1 or 2 clear the histogram and start it; 0 stops it and keeps the data readable.
PARAM_HIST_X · Access: set, read · Kept by Save: no
0 off, 1 electrical angle, 2 encoder (256 bins each; outside: 0)
35 The signal summed per bin. Set it before 34.
PARAM_HIST_Y · Access: set, read · Kept by Save: no
signal 0-18 (outside: 0). Default 3, Iq setpoint
36 Samples summed since the start. The histogram stops by itself when one bin holds 65535.
PARAM_HIST_SAMPLES · Access: read only · Kept by Save: no
samples
39 The samples per channel a capture holds.
PARAM_CAPTURE_LENGTH · Access: read only · Kept by Save: —
1024

Loop time

No. What it is Value
66 The control interrupt's checks (errors, watchdog).
PARAM_PROFILE_CHECKS · Access: read only · Kept by Save: —
0.1 µs, a running average over about 64 loops
67 Reading the encoder, the currents and the supply voltage.
PARAM_PROFILE_READ · Access: read only · Kept by Save: —
0.1 µs, a running average over about 64 loops
68 Sin, cos and the current transform.
PARAM_PROFILE_TRANSFORM · Access: read only · Kept by Save: —
0.1 µs, a running average over about 64 loops
69 The control mode, its loops and the PWM.
PARAM_PROFILE_CONTROL · Access: read only · Kept by Save: —
0.1 µs, a running average over about 64 loops
70 The rest of the interrupt (the capture).
PARAM_PROFILE_REST · Access: read only · Kept by Save: —
0.1 µs, a running average over about 64 loops
71 The ADC and the encoder read by register instead of through the library calls; about 14 µs less per loop.
PARAM_FAST_READ · Access: set, read · Kept by Save: no: on at every start-up
1 on, 0 off. Default 1
72 The PWM compare registers written directly; about 4 µs less per loop.
PARAM_FAST_PWM · Access: set, read · Kept by Save: no: on at every start-up
1 on, 0 off. Default 1

Sound

None of the sound settings is saved; see Sound.

No. What it is Value
80 What the sound is doing; a host that refills the queue or the sample buffer reads it.
PARAM_SOUND_STATE · Access: read only · Kept by Save: —
bits 0-7 events queued, 8-18 samples buffered, 24 a tone sounds, 25 the queue plays, 26 samples play, 27 the samples ran dry
81 The sound's voltage at most, all tones and samples together.
PARAM_SOUND_LIMIT_MV · Access: set, read · Kept by Save: no: 2000 at every start-up
mV, 0-6000 (outside: refused). Default 2000; 0 refuses sound and stops what plays
82 Which axis carries the sound. The q axis makes torque, a small ripple at the tone's pitch, and was much louder on the bench; the d axis makes no torque and is quieter.
PARAM_SOUND_AXIS · Access: set, read · Kept by Save: no: 1 at every start-up
1 the q axis (default), 0 the d axis (outside: refused)

Status

No. What it is Value
79 What is in force and what is running, one bit each.
PARAM_FEATURES · Access: read only · Kept by Save: —
bits, see What is in force
83 The stack margin: RAM between the heap and the stack that the stack has not used since start-up (setup() fills it with a pattern at its end, and this counts the bytes the pattern is still in). The stack needs about 1.5 to 2 KB of the about 7 KB there are; a value far below that means the drive is short of RAM.
PARAM_STACK_UNUSED · Access: read only · Kept by Save: —
bytes; -1 if it was not measured
84 The git commit the firmware was built from. #Info prints it as Build:, with a + for bit 28.
PARAM_BUILD_COMMIT · Access: read only · Kept by Save: —
the commit's first 7 hex digits as a number (bits 0-27); bit 28 set: built with uncommitted changes; 0 when git was not available at the build
85 When the firmware was built.
PARAM_BUILD_TIME · Access: read only · Kept by Save: —
Unix seconds, UTC; 0 when the build did not set it
86 This board: the chip's factory-unique 96-bit number folded into 32 bits. It never changes, also not with a new firmware or #Default. #Info prints it as Board ID:, 8 hex digits.
PARAM_BOARD_ID · Access: read only · Kept by Save: —
32 bits, read as unsigned
87 A new number at every successful #Cal, #Calonly or #Calangle, so a host can tell one calibration from the next. Send_Save_config keeps it, and #Default sets it back to 0. #Info prints it as Calibration ID:, 8 hex digits.
PARAM_CALIBRATION_ID · Access: read only · Kept by Save: yes, settings block 2
32 bits, read as unsigned; 0 before the first calibration
93 The gripper's stroke between positions 0 and 255, from its last calibration (Gripper mode). Added in firmware 110.
PARAM_GRIPPER_STROKE · Access: read only · Kept by Save: no: the gripper calibrates after every power-up
ticks; 0 while the gripper is not calibrated since power-up

What is in force: parameter 79

Parameter 79 says in one read what the drive runs with. #Info prints the same at its end, under In force:. Bit 0 is the least significant.

Bit Set when
0 the motor is calibrated
1 an encoder table is measured (in RAM)
2 the encoder table is in use (parameter 53)
3 an anti-cogging set is in RAM (harmonics or table)
4 anti-cogging is on (parameter 37 not 0)
5 anti-cogging is on as the table (otherwise as the harmonics)
6 the anti-cogging set in RAM is the one saved in the EEPROM
7 a current-sense zero trim is applied (parameter 59 or 60 not 0)
8 the current-sense zero measured with the bridge switching is in use (parameter 46)
9 commutation delay compensation is on (parameter 64 not 0)
10 the speed estimate is a PLL (parameter 50 is 1 or 2)
11 fast reading is on (parameter 71)
12 fast PWM is on (parameter 72)
13 sin and cos come from the integer table (parameter 65)
14 the position input filter is on (parameter 74 not 0)
15 the velocity-integral deadband is on (parameter 75 not 0)
16-17 parameter 56: what follows a #Calangle, 0 nothing, 1 or 2 the anti-cogging
20 a calibration is running (also #Calangle's search)
21 the encoder table is being measured
22 the anti-cogging is being identified
23 the runs after a calibration are about to start
24 sound is playing (Sound)

Bits 18, 19 and 25 to 31 are 0.

Reading the capture

A capture records three signals inside the control loop, one sample every divider loops, 1024 samples per channel. It starts when parameter 28 is written: at once (1), when the error flag rises (2, a watchdog trip included), or when channel A rises (3) or falls (4) through the level of parameter 29. Parameter 30 keeps that many samples from before the trigger. Status and diagnostics shows a whole capture.

  1. Set the signals (24, 25, 26), the divider (27), the pre-trigger (30) and, for 3 and 4, the level (29).
  2. Write the trigger (28). Parameter 31 reads 1 (armed), 2 (recording), then 3 (done).
  3. Read parameter 32 (samples readable) and 33 (the trigger sample's index, −1 if none).
  4. Send_Buffer_Read with kind 0, first 0, count = parameter 32: one Respond_Buffer_Data frame per sample, oldest first.

The histogram works the same way with parameters 34 to 36 and kind 1: it adds a signal into 256 bins by the electrical angle or by the encoder, every control loop, until it is stopped or one bin holds 65535 samples.

Comments