Errors and LED states

The LED

Pattern State
three short flashes, a pause normal operation: calibrated, no error
fast flashing, about ten times a second calibration running
a few flashes, then blinking for about 2 s after power-up the bootloader waits for a host before it starts the firmware; it keeps blinking when there is no valid firmware
on, steady error mode, or not calibrated
off no power, or #LED 0
Normal operation Calibration Error mode
Three short flashes and a pause Fast flashing during calibration On, steady

The error flags

The flags as the firmware keeps them, the line #Error prints for each, and where each sits in the two bytes of Send_Respond_State_of_Errors (bits numbered from the most significant).

Flag #Error prints Byte, bit Raised when
Error In error state! 0, 7 any of the flags below is set (also the error bit of every CAN identifier)
temperature_error Temp error 0, 6 the thermistor reads above #Tlim (with #Term 1)
encoder_error Encoder error 0, 5 the encoder reports no magnet (too weak a field)
Vbus_error Vbus error 0, 4 the supply is below 9 V or above #Vmax (29000 mV after #Default)
Driver_error Driver error (undervoltage, thermal shutdown, or overcurrent) 0, 3 never in this firmware; reserved (STEPFOC reads no fault output of its driver stage)
Velocity_error Velocity error 0, 2 the speed exceeds 30,000,000 ticks/s, a fixed threshold (Velocity_limit_error), not #Vlimit
Current_error Current error 0, 1 never in this firmware; reserved
ESTOP_error Received ESTOP command 0, 0 Send_ESTOP was received
Calibrated (0) Not calibrated 1, 7 (1 = calibrated) the motor has not been calibrated
Activated — 1, 6 the activated flag, not an error
Watchdog_error Watchdog error 1, 5 the watchdog time passed without a motion frame or a status request

Gripper mode has its own flags in Respond_Gripper_data_pack: a temperature error (a copy of the thermistor error), a timeout error (a copy of the CAN watchdog error, not a move timeout) and an E-stop error, which stays while the E-stop bit is 1; see the Gripper reference.

Clearing

#Clear and Send_Clear_Error clear every flag except Calibrated and go to idle; a flag whose cause persists is set again at once. The watchdog, E-stop and velocity errors clear and stay clear; the Vbus, encoder and temperature errors come back until the cause is gone, and so does a gripper E-stop while its E-stop bit is 1. Calibration clears the calibration error.